Remove existing paving slab and replace according to plan

Janet requested 3 quotes from Concreters in Wheelers Hill

  SUB BASE
------------------------------
Remove existing paving slab concrete as required. Locate any soft spots or poor ground and remove.

Disturbed areas 300mm below finished ground surface will be replaced with silty clay of similar plasticity to the natural soils on site. Which will be placed on 100mm layers and compacted to 95% S.D.D 3% O.M.C.

BASE
------------------------------
Class 3 40c FCR placed in 100mm layers and compacted to 96% S.D.D. 3% O.M.C.

Area is 7800mm x 3000mm


SLAB
------------------------------
0.2 mm VAPOUR BARRIER 300 mm LAPPED AND TAPED 100 mm THICK SLAB 1 LAYER SL-82 35 mm COVER 20 Mpa CONCRETE PLACED, COMPACTED AND CURED AS PER AS 3600 HB67

Finish concrete to drains.

Note that you will be working under a civil engineer who has recommended the following slab. If you have a plumber that you prefer to work with who is a suitable licensed WATERPROOFING SPECIALIST, please let me know (we also need waterproofing of membrane and drainage)